DTKX Arc-Extinguishing Switchgear
Keywords:
DTKX arc-extinguishing switchgear. The device mainly consists of a three-phase combined overvoltage protector DTGB, high-voltage vacuum contactors JZ with phase-selective control capability, a microcomputer controller, high-voltage current-limiting fuse assemblies FU, and a voltage transformer PT equipped with an auxiliary secondary winding. Once a single-phase arc-ground fault occurs in the system, the microcomputer controller immediately identifies the fault type and phase, and sends an operation command to the vacuum contactor JZ corresponding to the faulty phase. The vacuum contactor JZ completes its closing action within approximately 30 milliseconds, thereby converting the intermittent arc-ground fault into a metallic ground fault. Before the vacuum contactor operates, the overvoltage is limited to a lower level by the three-phase combined overvoltage protector DTGB.
Address
No. 010, Riyuetan Road, Economic Development Zone, Luancheng District, Hebei Province